Dyna-tite cable locks and wire rope can be used for suspension in a variety of ways to accommodate most mechanical & HVAC construction applications.

 

Standard Assembly

STEP 1
Pull the release pin back and thread the wire rope into one locking channel in the cable lock.

Image 2

STEP 2
Pass the wire rope “tail” through (or around) the anchor point (Eyehook, Beam, or Purlin).

Image 2

STEP 3
Pull the release pin back and push the wire rope tail into the second locking channel in the cable lock.

Image 2

STEP 4
Prior to the load being applied, the wire rope can be adjusted in either direction.

Image 2

Adjusting the Cable Lock With the load off the wire rope and the Cable Lock, push the release pin in the direction of the arrow on the Cable Lock. This will release the locking pawl and allow the wire rope to be moved freely in either direction. (After a load has been applied it may be necessary to pull the cable slightly to disengage the teeth on the pawl). Be sure the load is fully supported before attempting an adjustment.

 

 

Optional Figure 8 Assembly (CL23 ONLY)

STEP 1
Thread the wire rope into the “through hole” in the CL23.

Image 2

STEP 2
Pass the wire rope “tail” through (or around) the anchor point (Eyehook, Beam, or Purlin).

Image 2

STEP 3
Pull the release pin back and push the wire rope tail into one locking channel in the CL23 and pull at least six inches of the wire rope through.

Image 2

STEP 4
Pass the other wire rope end through (or around) the bracket or fixture on the object to be suspended. return the wire rope to the CL23. Pull the release pin back and push at least six inches of wire rope through the remaining locking channel. For final adjustment see step 4 above in standard Assembly.

Image 2

 

 

APPLICATIONS:

Unit Hanging

Image 2

Rectangular Ductwork

Image 2

Spiral Ductwork - Low Clearance

Image 2

Spiral Ductwork - Two Cable Locks

Image 2

Spiral Ductwork -Figure 8 (CL23 ONLY)

Image 2

 

 

 

 

 

Image 2
Dyna-Tite Product Catalog >

Image 2
Dyna-Tite Engineer Binder >

Please be patient when downloading the Engineer Binder. It is a 67 page pdf.

 

 
See Our Video